Fault Code of the Month: ABB ACS880 Fault 2310, Output OverCurrent
Written By ERD Team
10/26/2026

Your ABB ACS880 has tripped on Fault 2310. The drive is down and the motor is stopped. You need to know what caused the trip, whether the drive has sustained damage, and how to get back in service.

This guide covers what Fault 2310 means in the ACS880 architecture and the seven most common causes. It walks through a step-by-step troubleshooting sequence, explains how to recognize internal hardware damage, covers repair options, and explains how to prevent recurrence.


Fault 2310 at a Glance

DriveABB ACS880 (industrial drive series)
Fault Code2310
Fault NameOutput OverCurrent
What Triggers ItOutput current exceeds the drive’s maximum current protection limit
Drive ResponseImmediate shutdown; motor coasts to a stop
Most Common CausesMechanical overload, motor insulation failure, incorrect motor parameters, damaged output cables, internal IGBT failure
ManufacturerABB

What Fault 2310 Is Actually Telling You

Fault 2310 means the output current measured at the ACS880 inverter stage has exceeded the maximum value the drive is configured to allow. The drive shut down immediately to protect the IGBT power modules, the motor, and the output cables from sustained overcurrent damage.

One ACS880 feature affects how this fault should be interpreted: ABB’s Direct Torque Control technology, or DTC. Unlike V/Hz drives, the ACS880 continuously monitors and controls both motor torque and flux in real time. DTC provides faster, more precise motor control. It also means the drive responds to current deviations more quickly than conventional V/Hz drives.

ACS880 overcurrent trips can therefore be triggered by current conditions that a V/Hz drive might absorb without faulting. Correct motor parameter entry and a properly completed motor ID run are therefore particularly important on the ACS880. A drive that has never had a motor ID run performed is more susceptible to Fault 2310 than one that has been properly commissioned.

The cause of Fault 2310 can originate anywhere from the incoming power supply to the driven machine. Determining which system is responsible is what the troubleshooting sequence below is designed to identify.


Seven Common Causes of Fault 2310

1. Mechanical Overload

Excessive mechanical load is the most common cause of Fault 2310. When the driven machine requires more torque than the motor can supply, the drive faults before the motor stalls. Seized bearings, jammed conveyors, blocked pumps, and mechanical binding all produce overcurrent conditions at the drive output.

Mechanical overload faults typically exhibit a recognizable pattern. Motor acceleration strains as current rises progressively. The fault trips at or near the current limit threshold, sometimes with an audible indication from the motor. A fault that consistently occurs at the same point in the machine cycle points to a mechanical cause as the first investigation.

2. Motor Winding or Insulation Failure

Degraded motor insulation or a winding fault creates a low-resistance path between phases or between a winding and the motor frame. Current flows through that path in addition to the normal motor circuit, producing demand that exceeds the protection limit.

Insulation failure develops gradually in most cases. The fault may appear intermittently at first, particularly at high motor temperatures or high humidity, before becoming a consistent trip. A megohmmeter test on the motor windings with the drive output disconnected confirms or eliminates this as a cause. Do not reconnect the motor or reset the drive if the insulation test indicates failure.

3. Damaged Output Cables

The cables between the ACS880 and the motor experience vibration, heat, and environmental stress over time. Insulation damage, pinched cable sections, moisture inside conduit, and loose terminals can all create partial short-circuit conditions. Each produces intermittent overcurrent trips. This cause is common in applications where cables flex repeatedly, pass through conduit with tight bends, or contact mechanical surfaces.

Cable faults are frequently intermittent and difficult to locate without systematic testing. Megger testing the cables with both the drive output terminals and the motor terminal box disconnected is the correct method. A resistance measurement alone will not identify a fault that appears only when voltage is applied.

4. Acceleration Time Too Short

Accelerating a motor requires torque, and torque requires current. When the programmed acceleration time is shorter than the load’s rotational inertia can accommodate, the drive demands more current than the protection limit allows. Fault 2310 trips before the motor reaches operating speed.

High-inertia loads are most susceptible: large fans, centrifuges, heavy rotating equipment, loaded conveyors, and pump systems with significant fluid inertia. Extending the ramp time is often the simplest fix for Fault 2310 that occurs consistently during startup. If the application requires faster acceleration than the combination can supply, a higher-rated drive is the correct solution.

5. Incorrect Motor Parameters or Missing ID Run

The ACS880’s DTC algorithm depends on accurate motor nameplate data to compute the correct torque and flux commands. If the entered values differ from the actual motor, the drive applies incorrect current limits and control gains. Current demand under normal load conditions can trigger Fault 2310 even when nothing is wrong with the motor or the machine.

This cause is common after a motor replacement, a drive parameter reset, or when the original commissioning was incomplete. Beyond parameter accuracy, the ACS880 should have a motor ID run performed during commissioning. The ID run measures the actual motor electrical characteristics and calibrates the DTC algorithm to the specific motor installed. A drive never ID-run on its motor, or ID-run on a different motor, is operating on assumptions rather than measurements.

6. Output Phase Short Circuit

A short circuit in the output circuit, whether at the motor terminals, an output contactor, a cable junction box, a terminal strip, or the brake resistor wiring, creates a near-zero resistance load that draws current far in excess of the protection limit. The fault triggers essentially instantaneously. There is no progressive current rise; the trip happens as soon as the drive attempts to energize the output.

Output phase shorts are among the most urgent causes of Fault 2310 to identify and clear. Continued restart attempts without locating a short circuit risk IGBT damage from repeated current surges at each startup.

7. Internal Drive Hardware Failure

When external causes have been systematically ruled out and Fault 2310 persists, the fault likely originates inside the drive. IGBT module failures, gate driver faults, current sensor failures, and DC bus degradation can all produce output overcurrent with no external cause.

The clearest indicator of internal hardware failure is Fault 2310 tripping at power-up or after reset with the motor output disconnected. No external condition produces this pattern. Once this presentation is identified, the correct response is professional component-level evaluation rather than continued restart attempts.


Fault Patterns That Help Identify the Cause

The pattern of when and how Fault 2310 occurs is diagnostic information. Record it before resetting.

  • Fault during acceleration, consistently at the same speed: points to mechanical overload, insufficient ramp time, or load inertia that exceeds the drive’s torque capability at that acceleration rate
  • Fault at a consistent machine position or load state: indicates a mechanical condition that loads the motor beyond its rated capacity at that specific operating point
  • Fault on startup only, with no abnormal behavior at running speed: suggests acceleration time or starting torque configuration
  • Intermittent fault with no consistent pattern: points to cable insulation degradation, power quality disturbances, or marginal internal components beginning to fail
  • Fault immediately at power-up or immediately after reset: indicates internal hardware failure; discontinue restart attempts and submit the drive for professional evaluation
  • Fault only when motor is hot: suggests motor insulation degradation that appears only at elevated temperature

The ACS880 fault log retains fault history with timestamps. Pull that log and record it before clearing the buffer. Pattern data collected over multiple fault events is far more diagnostic than a single fault observation.


Step-by-Step Troubleshooting

Work through these steps in sequence. Confirm each item before proceeding. Follow ABB safety procedures and lockout/tagout requirements before performing any electrical testing on the drive or connected equipment.

Steps 1 to 4: Mechanical, Motor, and Cable Checks

  1. Record the fault context and pull the fault log. Before resetting, access the ACS880 fault history via the drive keypad or ABB Drive Composer software. Record the fault code, timestamp, output current value at fault, operating state, and any additional fault data displayed. This information is the diagnostic foundation for everything that follows.
  2. Inspect the driven machine for mechanical causes. Verify that the driven equipment rotates freely by hand or by safe manual jog. Check for product jams, seized bearings, blocked pump discharge, gearbox binding, or any mechanical condition that would increase load torque. Mechanical causes are the most common source of Fault 2310 and should be eliminated first.
  3. Test motor and cable insulation resistance. Disconnect the motor cables at both the ACS880 output terminals and the motor terminal box. Perform insulation resistance testing on the cables and motor windings separately. Compare results to the motor manufacturer’s minimum specification and to previous measurements if available. A failed insulation test confirms a wiring or motor cause before any drive component is implicated.
  4. Inspect output cables and connections physically. Examine cables for visible insulation damage, crushing, or abrasion. Check conduit entry points for cable pinch or moisture infiltration. Inspect all terminal connections at the drive output, cable junction points, and motor terminal box. Tighten any loose terminals. Look for discoloration or burn marks that indicate a connection running hot.

Steps 5 to 8: Drive Parameters, Power Quality, and Internal Evaluation

  1. Verify motor parameters and ID run status. Access the motor data group and confirm that rated current, rated voltage, rated power, rated frequency, and rated speed match the motor nameplate. Confirm that a motor identification run has been performed on the installed motor. If no ID run has been completed, or if a motor replacement occurred without a new ID run, perform it before investigating other causes.
  2. Review and adjust acceleration and torque limit settings. Check the programmed acceleration ramp time against the load characteristics. For high-inertia loads or applications where Fault 2310 occurs during startup, increase the ramp time incrementally and test. Verify that torque limit parameters are set correctly for the application.
  3. Measure incoming supply voltage and phase balance. With the drive powered under normal operating conditions, measure input voltage on all three phases at the drive terminals. Calculate the voltage imbalance percentage. Check incoming terminals for looseness or heat damage. Verify that all three phases are present and stable during motor starts.
  4. Submit the drive for professional evaluation if Fault 2310 persists. If Fault 2310 persists after verifying mechanical conditions, insulation, cable condition, motor parameters, and supply voltage, the drive likely has internal power section damage. Component-level electronic evaluation is the appropriate next step. Continued restart attempts without resolving an internal fault risk further IGBT and gate driver damage.

When Fault 2310 Indicates Internal Drive Damage

Several presentations specifically indicate that the fault originates inside the ACS880 rather than from an external condition.

Fault 2310 tripping at power-up, before any run command and with the motor output disconnected, is the clearest indicator of internal failure. No load condition can produce this. A shorted IGBT module, a gate driver fault, or a current sensor failure is the typical finding.

Fault 2310 recurring consistently within minutes of restart, even under very light load, suggests thermal-related IGBT degradation. IGBTs that have been stressed by prior overcurrent events may operate briefly before failing again as they warm up. Each restart cycle adds additional stress to partially damaged devices.

Burn marks on boards or module assemblies, damaged components, or melted connector bodies confirm internal damage regardless of fault pattern. This evidence justifies immediate professional evaluation without further restart attempts.

Components Typically Involved in ACS880 Fault 2310 Repair

Component-level failures associated with overcurrent events in the ACS880 typically involve IGBT power modules with collector-emitter short circuits or open failures, gate driver circuits with damaged driver ICs or isolation components, current sensor circuits producing incorrect measurements, DC bus capacitors causing voltage transients during switching, and damaged snubber circuits. Any of these can produce Fault 2310 independently or in combination.


Repair vs. Replace: The Cost Decision

For many facilities, repairing an ACS880 drive is significantly more economical than replacing it. The ACS880 is a premium drive platform with corresponding hardware costs. Repair returns a drive to full operation at a fraction of replacement cost. No programming migration, no new commissioning, and no wiring changes are required.

OptionTypical CostTypical Lead Time
Professional electronic repair25 to 45% of replacement costDays to a few weeks
New OEM replacement drive100% of purchase priceSeveral weeks to months, depending on model

For ACS880 models that have been discontinued or are approaching end of OEM support, repair may be the only option that avoids both long lead times and full commissioning work. For the complete ROI framework on this decision, see Industrial Electronic Repairs That Pay for Themselves.


Preventing Future Fault 2310 Events

Once the immediate cause has been addressed, a structured preventive program reduces the likelihood of recurrence.

  • Inspect ACS880 cooling fans every six months. Fan bearing degradation reduces airflow before the fan stops. Thermal stress is a primary driver of IGBT aging in drives running continuously in warm environments.
  • Clean heat sinks and air passages during scheduled maintenance. Dust accumulation on heat sink fins reduces cooling efficiency directly and compounds thermal stress on power components.
  • Perform motor insulation resistance testing annually, particularly in environments with high humidity, thermal cycling, or chemical exposure. Catching insulation degradation early prevents the overcurrent transients that damage IGBTs.
  • Monitor output current trends over time. A motor drawing consistently higher current than at initial commissioning is either mechanically degrading or developing winding changes. Both conditions produce Fault 2310 eventually if not addressed.
  • Tighten power terminals annually. Thermal cycling loosens connections over time, and loose terminals produce resistance, heat, and current irregularities that stress drive output components.
  • Back up ACS880 parameter sets after any commissioning change. A current parameter backup eliminates the recommissioning work that a drive failure or replacement would otherwise require.
  • Review the drive fault log regularly, not just after trips. Overcurrent warnings that appear in the log before a fault event indicate a developing condition. Proactive maintenance can address it before a production stoppage occurs.

ERD Repairs ABB ACS880 Drives

ERD Ltd. Inc. has been repairing industrial variable frequency drives since 1995. Our engineer-owned facility in Kernersville, North Carolina provides component-level diagnosis and repair of ABB ACS880 drives. Coverage spans the full product family, including standard, multiaxial, and regenerative configurations.

We also repair drives from Allen-Bradley, Siemens, Danfoss, Yaskawa, Mitsubishi, Schneider Electric, and many other manufacturers. Every repair begins with root cause diagnosis at the component level. Repairs are tested under load before return. Original parameters and commissioning data are preserved throughout the repair process. Every repair is backed by our 3-year warranty.

If your ACS880 is displaying Fault 2310 after operating conditions have been verified, ERD can evaluate the drive and identify what failed. A fully tested unit is returned ready for production.

Have an ABB ACS880 displaying Fault 2310 or another persistent fault? Submit a repair request or contact our team. We will assess it quickly and give you a clear answer on repair cost and timeline.